X20BC1083 X20 Bus Controller POWERLINK

Products Mode: X20BC1083
Place of Origin: AT

Inquery Now
Description
X20BC1083 X20 Bus Controller POWERLINK 
 
MATERIAL NUMBER:
X20BC1083
DESCRIPTION:
  • POWERLINK
  • I/O configuration and firmware update via the fieldbus
  • Integrated hub for efficient cabling
  • Up to 2 slots for interface modules

The bus controller makes it possible to connect X2X Link I/O nodes to POWERLINK. It is also possible to operate the X2X Link cycle synchronously 1:1 or synchronous to POWERLINK using a prescaler.

POWERLINK is a standard protocol for Fast Ethernet equipped with hard real-time characteristics. The POWERLINK Standardization Group (EPSG) ensures that the standard remains open and is continually developed:: www.ethernet-powerlink.org.

The bus modules expanded to the left allow connection of up to 2 interface modules in addition to the bus controller.

Short description
Bus controller POWERLINK (V1/V2) controlled node with up to 2 slots for interface modules
General information
B&R ID code 0x2268
Status indicators Module status, bus function
Diagnostics  
Module status Yes, using LED status indicator and software
Bus function Yes, using LED status indicator and software
Power consumption  
Bus 2 W
Additional power dissipation caused by actuators (resistive) [W] -
Certifications  
CE Yes
UKCA Yes
ATEX Zone 2, II 3G Ex nA nC IIA T5 Gc
IP20, Ta (see X20 user's manual)
FTZÚ 09 ATEX 0083X
UL cULus E115267
Industrial control equipment
HazLoc cCSAus 244665
Process control equipment
for hazardous locations
Class I, Division 2, Groups ABCD, T5
DNV Temperature: B(0 - 55°C)
Humidity: B(up to 100%)
Vibration: B(4 g)
EMC: B(bridge and open deck)
LR ENV1
KR Yes
ABS Yes
EAC Yes
KC Yes
Interfaces
Fieldbus POWERLINK (V1/V2) controlled node
Type Type 2 
Variant 2x shielded RJ45 (hub)
Line length Max. 100 m between 2 stations (segment length)
Transfer rate 100 Mbit/s
Transfer  
Physical layer 100BASE-TX
Half-duplex Yes
Full-duplex No
Autonegotiation Yes
Auto-MDI/MDIX Yes
Hub propagation delay 0.96 to 1 µs
Min. cycle time   
Fieldbus 200 μs
X2X Link 200 μs
Synchronization between bus systems possible Yes
Cyclic data  
Input data Max. 1488 bytes
Output data Max. 1488 bytes
Electrical properties
Electrical isolation POWERLINK isolated from bus and I/O
Operating conditions
Mounting orientation  
Horizontal Yes
Vertical Yes
Installation elevation above sea level  
0 to 2000 m No limitation
>2000 m Reduction of ambient temperature by 0.5°C per 100 m
Degree of protection per EN 60529 IP20
Ambient conditions
Temperature  
Operation  
Horizontal mounting orientation -25 to 60°C
Vertical mounting orientation -25 to 50°C
Derating -
Storage -40 to 85°C
Transport -40 to 85°C
Relative humidity  
Operation 5 to 95%, non-condensing
Storage 5 to 95%, non-condensing
Transport 5 to 95%, non-condensing
Mechanical properties
Note Order 1x terminal block X20TB12 separately.
Order 1x power supply module X20PS9400 or X20PS9402 separately.
Order 1x bus base X20BB81 or X20BB82 separately.
Pitch   
X20BB81 62.5+0.2mm
X20BB82 87.5+0.2mm